Product introduction:
1 Tests for Current Transformer:
1 Excitation curve and parameters test
2 Turns ratio test
3 Ratio and phase error test
4 Polarity mark check
5 Winding resistance measurement
6 Secondary loop burden measurement
7 Error line curve test for protection CT
8 Transient CT parameters test
9 CT nameplate guess
10 Saturation hysteresis loop curve measurement
1 Tests for potential transformer
1 Turns ratio test
2 Ratio error and phase angle error test
3 Polarity test
4 Secondary burden test
5 Winding resistance test
Product technical index:
1 Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
2 Power supply: AC220V±10%, 50/60Hz±10%
3 Voltage output: 0.1~180V (AC)
4 Current output: 0.001~5A(RMS)
5 Power output: 500VA
6 Maximum knee voltage measurement: 45KV
7 Current measurement:
Range: 0~10A (automatically change range in 0.1/0.4/2/10A)
Error: <±0.1%+0.01%FS
8 Voltage measurement:
Range: 0~200V (automatically change range in 1V/10V/70V/200V)
Error: < ±0.1%+0.01%FS
9 Turns ratio measurement:
Range:1~35000
1~2000 error<0.05%
2000~5000 error<0.1%
5000~35000 error<0.2%
10 Phase measurement: error: ±2min; resolution: 0.01min
11 Winding resistance measurement:
Range: 0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
Error: < 0.2%RDG+0.02%FS
Maximum resolution: 0.1mΩ
12 Temperature measurement:-50~100 Celsius degree; error<3 Celsius degree
13 CT Secondary burden:
Range: 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
Error: <0.2%RDG+0.02%FS
Maximum resolution: 0.001ohm
14 PT Secondary burden:
Range: 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
Error :<0.2%RDG+0.02%FS
Maximum resolution: 0.1ohm Product Tags: