Wuhan Huaying Electric Power Tech & Science Co.,ltd

Manufacturer leader for electrical test equipment in central China.

Manufacturer from China
Verified Supplier
12 Years
Home / Products / All Products /

HYVA-404 CT PT Analyzer

Contact Now
Wuhan Huaying Electric Power Tech & Science Co.,ltd
Visit Website
City:Wuhan
Province/State:Hubei
Contact Person:Ms. Amy Wang
Contact Now

HYVA-404 CT PT Analyzer

Ask Latest Price
Video Channel
Place of Origin :Wuhan,Hubei,China
Brand Name :Huaying
Certification :ISO CE
Model Number :HYVA-404
MOQ :1 set
Price :email whhy818@163.com
Packaging Details :wooden case
Delivery Time :7 working days
Payment Terms :T/T L/C
Supply Ability :200 sets per month
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Introduction

Tests for Current Transformer:
1)Excitation curve and parameters test
2)Turns ratio test
3)Ratio and phase error test
4)Polarity mark check
5)Coil resistance measurement
6)Secondary loop burden measurement
7)Error line curve test for protection CT
8)Transient CT parameters test
9)CT nameplate guess
10)Saturation hysteresis loop curve measurement

Tests for Voltage Transformer:

1)Turns ratio test and phase angle error test
2)Polarity test
3) Secondary burden test
4) Coil resistance test

Application

1) CT nameplate check
2) CT parameters check in work burden
3) CT transient parameters analysis
4) CT ratio and phase error calibration
5) PT routine test

Technical index

1 Test standards: IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13
2 Power supply: AC220V±10%,50Hz/60Hz±10%
3 Power output: 0.1~180V (AC)
4 Current output: 0.001~5A(RMS)
5 Power output:300VA
6 Maximum knee voltage measurement:45kv
7 Current measurement:
Range:0~10A (automatically change range in 0.1/0.4/2/10A)
Error <±0.1%+0.01%FS
8 Voltage measurement:
Range:0~200 V (automatically change range in 1V/10V/70V/200V)
Error < ±0.1%+0.01%FS
9 Turns ratio measurement:
Range :1~35000,
1~2000 error<0.05%
2000~5000 error>0.1%
5000~35000 error<0.2%
10 Phase measurement: error:±2min,resolution:0.01min
11 Coil resistance measurement:
Range:0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
Error< 0.2%RDG+0.02%FS
Maximum resolution:0.1mΩ
12 Temperature measurement:-50~100 Celsius degree, error<3 Celsius degree
13 CT Secondary burden:
Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
Error <0.2%RDG+0.02%FS
Maximum resolution 0.001ohm
14 PT Secondary burden:
Range 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
Error <0.2%RDG+0.02%FS
Maximum resolution: 0.1ohm
15 PT ratio measurement:
Range :1~35000,
1~5000 error<0.2%
5000~35000 error<0.5%
16 Saved data groups:>1000groups
17 Work condition: Temperature:-10℃~50℃, moist:≤90%
18 Size: 485mm×356mm×183mm
19 Weight: <15Kg

Tags

ct analyzer, ct pt analyzer, current transformer analyzer, potential transformer analyzer,testing equipment,lab test equipment,made in china, alibaba gold supplier,measuring and testing equipment.

HYVA-404 CT PT Analyzer