1. Product Name:

CT PT Analyzer HYVA-402V

2. Equipment Description:

1 Turns Ratio, ratio error and phase error test

2 Polarity test for CT

3 Excitation curve and knee voltage measurement in power frequency for CT

4 Error curve test

5 Coil resistance test for CT and PT

6 Secondary burden test for CT

7 Turns ratio test for PT

8 Polarity test for PT

9 Excitation curve test for PT

10 Coil resistance test for PT

3.Technical Parameters:

1 Output voltage:0~2000V(RMS)

2 Test frequency: power frequency (50Hz/60Hz)

3 Output Current:0~5A

4 Maximum output power:2KVA

5 Maximum knee voltage measurement: 2000V

6 Range of turn ratio:

1~10000,error 0.5%RDG,

10000~30000,error 1%RDG

7 Range of voltage measurement:

0~50V(RMS),error 0.5%RDG+0.05%FS

0~600V(RMS), error 0.5%RDG+0.05%FS

0~2000V(RMS), error 0.5%RDG+0.05%FS

8 Range of current measurement:

0~50mA(RMS),error 0.5%RDG+0.05%FS

0~1A(RMS), error 0.5%RDG+0.05%FS

0~5A(RMS),error 0.5%RDG+0.05%FS

9 Test current of coil resistance:0.11A

10 Test error of coil resistance:

0~5 Ω, error 0.5%RDG+0.05%FS

0~50Ω, error 0.5%RDG+0.05%FS

0~100Ω,error 0.5%RDG+0.05%FS

11 Test Current of secondary burden:0.11A(RMS)

12 Test error of secondary burden:

0~5Ω, error 0.5%RDG+0.05%FS

0~50Ω, error 0.5%RDG+0.05%FS

Power factor error:0.5%RDG+0.05%FS

13 Power supply:AC220V±10% 50Hz/60Hz